python.d/sensors: Increase voltage limits 127 -> 400 (#15905)
* Fix a limit that caused my properly functioning PMBus power supply
sensor to be skipped as it reported 208VAC.
* The 400V limit was pulled from the Open Compute Project M-CRPS
specification v1.0 Section 5.1.3.2[0] which defines a power supply
input voltage as 380VDC and specifies a Vmax of 400VDC.
* Also decrease the lower limit to -400VDC as some telecom power
supplies may report negative voltage, most notable is -48VDC and
expect more could as well.
Diffstat (limited to 'collectors/python.d.plugin')
-rw-r--r-- | collectors/python.d.plugin/sensors/sensors.chart.py | 2 |
1 files changed, 1 insertions, 1 deletions
diff --git a/collectors/python.d.plugin/sensors/sensors.chart.py b/collectors/python.d.plugin/sensors/sensors.chart.py index 701bf64147..0d9de3750f 100644 --- a/collectors/python.d.plugin/sensors/sensors.chart.py +++ b/collectors/python.d.plugin/sensors/sensors.chart.py @@ -66,7 +66,7 @@ CHARTS = { LIMITS = { 'temperature': [-127, 1000], - 'voltage': [-127, 127], + 'voltage': [-400, 400], 'current': [-127, 127], 'fan': [0, 65535] } |